Energy Meter Test Bench for Electrical Utilization Managment Terminal

Energy Meter Test Bench for Electrical Utilization Managment Terminal
Product name : Energy Meter Test Bench for Electrical Utilization Managment Terminal
Item : PEC-T-ZDYA-16
Details :
PEC-T-ZDYA-16 is specially designed for load management terminal, distribution/substation monitoring and measurement terminals to measure comprehensive errors. It can be utilized in labs to measure and evaluate functions, performances and field applicability of various electrical instruments.
It is applicable to factory testing (for electrical utilization management terminal manufacturers), product test before acceptance (for electrical measurement management institutes), and product examination (for lab of power institute).
It is a combination of controlling cabinet, measuring desk and application software. The whole system is consisted of programmable power source, multi function reference standard meter, meter holding table, GPS clock time source, communication ports, measuring ports, display/indication equipment, power loss measurement equipment, function simulators, auxiliary power supply, working station (PC, printer, barcode scanner) etc.
 
Main features:
Ÿ   Single testing mode and automatic testing mode for selection
Ÿ   Measurements of:
-        Open phase (of working power)
-        Rated value and permissible deviation (of working power)
-        Power loss
-        Power-off data and clock retention
-        Voltage dip and short interruption
Ÿ   Tests for data collection:
-        State quantity
-        Pulsed quantity
-        Analogue quantity of AC voltage and current
-        Analogue quantity of DC power
-        Data of energy meter
*       Statutes
*       Real time interrogation
*       Curve data
*       Daily data
*       Monthly data
*       Alarm events
Ÿ   Tests for data storing and processing
-        Real time data and current data
-        Historical daily data
-        Historical monthly data
-        Monitoring of energy running condition
-        Measurement of energy quality pass rate
-        Measurement of variable loss
-        Measurement of transformer running
-        Measurement of power outage
-        Measurement of harmonic
-        Data compression
Ÿ   Parameter setting and data querying
-        Clock interrogation and time pairing
-        Accuracy of terminal clock
-        Transformation ratio of PT/CT and time constant
-        Terminal parameters
-        Reading parameters
-        Limit parameters
-        Reactive power compensation parameters
Ÿ   Controls
-        Power limit setting closed-loop control and alarm
-        Power value limit setting closed-loop control and alarm
-        Remote control
-        Power supply assurance and exclusion
Ÿ   Event alarm and recording
Ÿ   Data transmission (GPRS mode preset, other modes for selection)
-        Communicate with master station via network channel
-        Communicate with master station via RS485 channel
-        Communicate with master station via GPRS channel
-        Communicate with master station via CDMA channel (optional)
-        Communicate with master station via 230M wireless power network
-        Communicate with master station via SMS channel
-        Reading terminal data via IR reader
-        Communicate with energy meter via RS 485 channel
Ÿ   Local function testing
Ÿ   Terminal maintenance
-        Self examination and self recovery
-        Terminal initialization
-        Version interrogation and remote upgrading (of terminal)
Ÿ   Measurement of GPS timing ability
Ÿ   Optional functions (Kehui’s patents):
-        Load capacity simulation test for downstream channel of collection terminal
-        RS 485 bus wiring length simulation test
-        RS 485 port receiving sensitivity simulation test
-        Immunity of frequency magnetic field test (via Kehui’s frequency immunity tester)
Technical data

General
Accuracy class of reference meter
0.05
Testing positions
16 (with automatic current short connection holder)
Downstream RS 485 bus
1~3 lines
Virtual energy meter RS 485 bus
1-2 lines
Intrinsic error of reference clock time source
≤±0.5×10-6
Size (L×W×H, mm)
Measuring desk: 2130×1850×650
Controlling cabinet: 600×800×1800
Three phase power source
Output voltage
3×100V, 3×57.7/100V, 3×220/380V ±20%
Output current
0.01A~25A
Output capacity
Voltage: 15VA/position
Current: 25VA/position
DC analogue quantity
4~20mA
Communication of master station (via)
 Network, GPRS, SMS(optional)
Local ports
IR, RS 232, RS 485, Pulse, alarm, switching value,  wheel control, gate node

 
[Next : PEC-T-ZDCA-16]→