Portable Three Phase Energy Meter Test Equipment

Portable Three Phase Energy Meter Test Equipment
Product name : Portable Three Phase Energy Meter Test Equipment
Item : PEC-H3A
Details :
² Accuracy classes: 0.05%, 0.1%
² Measurement of energy meter errors, display of voltage, current, power, power factor, frequency etc.
² Measurement of harmonics of 2nd  to 51st
² Measurement of clock error (of energy meter)
² Measurement of transformation ratio for CT
² Communication examination for energy meters
² Measurement for register
² Detection of wiring failures and calculation of electricity compensation
² USB and communication ports available
² Self adjusted clamp-on CT’s (KHPEC’s patent) provided
² Double of power supply via lithium battery or PT
 

Main features:
·           Automatic/manual measurement of single phase, three phase three wire, three phase four wire active and reactive induction energy meters and static energy meters (by sampling pulse)
·           Comparison measurement of voltage, current, power, power factor, phase, frequencyof other electric instruments and transmitter by
·           Measurement of secondary burden of PT and CT; proofreading of constant of energy meter; energy measurement of four quadrants
·           Simultaneous measurement of errors for active and reactive energy meters; simultaneous measurement of errors of master and sub meter; automatic calculation of standard deviation estimates
·           Simultaneous measurement of active and reactive errors for load management terminal and distribution/ substation monitoring terminals; measured data can be read and stored via RS 485 port or IR port
·           Equipped with RS485,RS232, IR and USB port
-       Via the USB port, information of customers and energy meter can be downloaded from the marketing management system; measured data can also be uploaded to the management system
-       KWh, voltage, current, power and phase angle ect of energy meter and management terminals can be read via RS485(RS232) or IR port; also, broadcasting or command (according to the reference meter) time pairing provided
·           Self adjusted clamp-on CT’s enable long term accuracy; minimum measuring range of current to 1mA (with 1A/5A clamp-on CT’s)
·           Wiring testing is accessible on a new no-load field (with PT/CT)
·           Barcode input via external scanner, ID number of energy meter and number of seal can be read, and easily input on site
·           Touch screen supports handwriting input
·           True reactive digital measurement technique, stable operation without influences of voltage/current unbalances, phase angle asymmetry and frequency changes; reactive accuracy to 0.1%
·           Stability is highly improved without the utilization of potential meter
·           5A clamp-on CT’s with 0.2 accuracy class provided
·           20A,100A,500A,1000A clamp-on CT’s for selection; transformation ratio of CT can be measured with the utilization of a 5A clamp-on CT’s meanwhile
·           Automatic diversion of voltage (30V~480V), 5A current direct input
·           Detection of regular wiring failures of three phase three wire(48), three phase four wire circuits(96); vector diagram display
·           Measurement of harmonics (2nd ~51st ), measured data can be stored
·           Simultaneous display of waves of three phases’ voltage and current
·           Data management
-        Measured data of 1000 energy meters can be stored including working parameters for further analysis
-        Communicable to PC, convenient connection to existing data base and management system; PEC Energy Meter Management System software is provided (optional)
-        With the utilization of a flash disk and upgrade software, measured data can be uploaded/downloaded at anytime
·           Double way of power supply via lithium battery or measured circuit
·           Light plastic enclosure design
Technical Data

General
Power supply
AC57~450V, 50~60Hz
Power consumption
About 10VA
Ambient temperature
-20--+40 (accuracyassured)
Relative humidity (not condensing)
40%-95%
Dimension(L×W×H, mm)
249×154×58
Weight
1.8Kg
Warm-up  time
< 3 minutes
Battery endurance
4 hours
LCD color display
5.7”, 320×240 TFT
Communication port
RS 232
Safety
Declaration of conformity
CE conformed
Operation reference
Measuring ranges
Voltage
AC 30~480V
Current:
 
Direct connection—1A, 5A
Via clamp-on CT’s: 5A, 20A(±0.2%, self adjusted), 100A, 500A, 1000A(±0.5%)
Frequency
45~65Hz
Phase
-180 º ~+180º
Constant of pulse
5A:       FL=3.6×104P/KWh FH=3.6×107P/KWh                               Others:  FL=36000×5/rated current (P/KWh)
     FH=3.6×107×5/ rated current (P/KWh)
Harmonic measurement
Range: 2nd ~51st 
Accuracy: ±0.01% (compared to 100% fundamental wave)
Transformation ratio deviation
< ±0.5%
Voltage deviation
< ±0.01%
Frequency deviation
< ±0.01%(45-55Hz)
Influence of temperature
< ±5ppm/ (typical)
Variation in 24hrs.
<±0.02% (class 0.1)
<±0.01% (class 0.05)
Intrinsic error
Current input ( via Clamp-on CT’s)
5A (self adjusted), 20A: ±0.2%   
100A, 500A, 1000A, 1500A: ±0.5%
Direct connection
 
Accuracy class: 0.1
Accuracy class: 0.05
Active energy
±0.1%                                                           
±0.05%
Reactive energy
±0.1%                                                           
±0.1%                                                           
Active power
±0.1%                                                           
±0.05%
voltage
±0.1%                                                            
±0.05%
current
±0.1%                                                           
±0.05%
Frequency
±0.05Hz
±0.05Hz
Phase
±0.1º
±0.05º

←[Previous : PEC-T-ZDDA-16] [Next : PEC-A]→